- Pressure ranges
- -100 kPa to 60 MPa across the series
- Pressure types
- Gauge, absolute and sealed gauge
- Accuracy
- 0.2, 0.25 or 0.5 grade, by range and configuration
- Output
- 4-20 mA two-wire; 0-5 V, 1-5 V or 0-10 V three-wire; RS-485 with Modbus
- Supply
- 10-32 V on the current output; 5-32 V on RS-485, depending on the display fitted
- Response time
- T90 ≤ 10 ms on current and voltage output; T90 ≤ 100 ms on RS-485
- Stability
- ±0.2%FS per year
- Overpressure
- 150%FS from 0.035 to 10 MPa; 125%FS from 10 to 60 MPa
- Process connection
- M20×1.5 as standard; M14×1.5, G1/4, G1/2 and others to order
- Sealing
- IP65
A pressure transmitter turns the pressure at a tapping point into a signal a control system can read. The instrument on this page uses a diffusion silicon sensing element and covers gauge, absolute and sealed gauge references, with a span from -100 kPa up to 60 MPa across the series. Output is 4-20 mA two-wire as standard, with 0-5 V, 1-5 V, 0-10 V and RS-485 Modbus available by configuration.
What distinguishes this series is not the element but the number of constructions built around it. The same measurement module is offered in a plain plug housing, a short housing for a tight installation, a finned housing for hot media, a housing with a four-digit display, a GX12 circular connector version, a flush-diaphragm sanitary version with a clamp connection, a die-cast aluminium housing, a flanged version, and forms with a 4G radio or a flameproof enclosure. That range exists because the element is small and the electronics are a circuit board; once those two are fixed, the housing is what decides where the instrument can be used.
How the housing decides where the transmitter can be used
The measuring element itself is a silicon diaphragm with a diffused resistor network, isolated from the process by a thin diaphragm and a fill fluid in industrial constructions. The medium therefore meets the wetted metal rather than the silicon, and the element stays at a temperature the compensation can handle. Everything the housing does follows from protecting that arrangement without distorting what it reads.
A finned housing moves heat away from the electronics, which is why a high-temperature construction exists at all: the limit is usually the circuit and the fill fluid rather than the diaphragm, and the fins buy back the difference. A flush diaphragm removes the dead volume in front of the element, so a medium that would stagnate or hold residue in a threaded port does not have anywhere to sit. A flameproof enclosure contains an internal fault rather than preventing it, which is why it changes what the instrument is permitted to be installed next to, and nothing about what it measures. A radio version removes the cable, which changes the installation cost far more than it changes the measurement.
Two figures move with the span rather than with the housing, and they are worth reading together. Temperature drift within the compensated range is 2%FS on spans from 10 to 60 kPa and 1.5%FS above that, and the compensated range itself is 0 to 60°C, 0 to 70°C or -10 to 70°C depending on the span band. A narrow span on a cold outdoor installation is therefore a different proposition from the same instrument indoors.
How to select the right transmitter
Settle the pressure type first. A gauge transmitter reads against local atmosphere and suits a pump discharge, a compressed air line or a vented tank. An absolute transmitter reads against a sealed vacuum and is the right choice where the barometric term must not appear in the reading. A sealed gauge transmitter holds a fixed internal reference and is used where a vented reference would fill with the medium. A compound range crossing zero is a fourth case again, and it is not interchangeable with a sealed gauge instrument of the same numeric span.
Then settle the span against the working pressure rather than the peak. The accuracy grade applies to the full scale of the span selected, so a range several times the normal working pressure spends its life reading a small fraction of full scale and reports less than it could. The published overpressure figure - 150%FS up to 10 MPa and 125%FS above it - covers short spikes such as a pump start or a line test, not a sustained overrange.
Then settle the environment, because that is what selects the housing: media temperature picks between the standard and finned constructions, the cleanliness requirement picks the flush diaphragm, the area classification picks the enclosure, and the distance to the control system picks between a loop and a radio. Media compatibility is the remaining item, and the supplied material does not state the diaphragm or port material, so an aggressive medium has to be raised with the enquiry rather than assumed.
Wiring, supply and load resistance
The supply range and the loop resistance are published together because one constrains the other. On the current output, the load a two-wire loop can drive is RL ≤ (U-10 V)/0.02 A without a local display and RL ≤ (U-14 V)/0.02 A with one, where U is the supply voltage. The difference between the two expressions is the voltage the display needs, and using the wrong one is how a loop that looked comfortable on paper reads low at the top of its range. On the voltage outputs the constraint is a minimum load of 5 kΩ rather than a maximum.
The supply itself changes with the output and the display: 10-32 V for 4-20 mA, 8-32 V for 0-5 V or 1-5 V, 12-32 V for 0-10 V, and on RS-485 either 8-32 V, 7-32 V or 5-28 V depending on whether a display is fitted and whether it is LCD or LED. The pin functions are not the same across the output forms, so the wiring is read from the form ordered rather than from the series in general.
Measurement limitations and selection considerations
A transmitter selected with far more span than the duty needs is the most common way to make a good instrument read poorly. The grade applies to full scale, so the error at the working point grows in proportion to how much of the span is unused.
Narrow spans on cold installations deserve a second look, because the compensated range narrows as the span narrows and the drift figure rises. Where the process sits at the bottom of a narrow span outdoors, a different sensing technology or a wider span may serve better than a tighter grade on the same instrument.
A transmitter is also the wrong instrument where the question is not continuous. If the requirement is a contact that changes state at a set point, a pressure switch does that without a loop; if the requirement is a local indication and nothing else, a gauge does it without a supply. Where the medium is aggressive, the answer is usually a separating diaphragm ahead of the instrument rather than a more exotic wetted metal, and where the medium pulses hard, the damping structure in the port helps but does not replace a proper snubber.
Configuration and ordering
The supplied material does not give a model code breakdown for the series, so a configuration is stated in words: pressure type, range, output form, supply, process connection, electrical connection, housing and lead length. That is also what a quotation needs, and it is the order in which the choices constrain each other - the output form fixes the supply range, the supply range fixes the load that can be driven, and the housing fixes the media temperature that applies.
Every value below is taken from source documentation. Where a parameter is not stated in the available material it is marked as information required rather than estimated.