Electromagnetic Flow Meters

An electromagnetic flow meter, usually shortened to magmeter, measures the volumetric flow of a conductive liquid. There is nothing in the bore but the liquid itself: the meter applies a magnetic field across a lined section of pipe and reads the small voltage that the moving liquid generates across two electrodes. Because nothing obstructs the flow, there is no pressure drop to account for and nothing for fibres, solids or slurry particles to catch on.

What an electromagnetic flow meter is

An electromagnetic flow meter, usually shortened to magmeter, measures the volumetric flow of a conductive liquid. There is nothing in the bore but the liquid itself: the meter applies a magnetic field across a lined section of pipe and reads the small voltage that the moving liquid generates across two electrodes. Because nothing obstructs the flow, there is no pressure drop to account for and nothing for fibres, solids or slurry particles to catch on.

That construction is why the type turns up wherever the medium is difficult. Waste water carrying grit, paper stock, mining slurry, chemical dosing lines and food or beverage streams that must be cleaned in place are all routine duties. The one hard precondition is conductivity - the liquid has to be conductive enough for the signal to be extracted at all - and the pipe has to run full. Those two conditions, rather than the accuracy class, decide whether a magmeter is the right instrument.

This page covers how to configure one: which liner and electrode a medium forces, what the installation has to provide, and which of the neighbouring flow technologies takes over the moment the medium stops being conductive or the pipe stops running full.

How an electromagnetic flow meter measures

The measurement follows Faraday’s law of induction. A conductor moving through a magnetic field develops a voltage proportional to its velocity, and for a given bore and field strength that voltage is proportional to the average flow velocity. The field is generated by coils outside the pipe, the electrodes pick up the signal from the liquid, and the liner keeps the signal from short-circuiting through the metal pipe body. The flow transmitter then converts velocity and known cross-section into a volumetric rate.

Two practical consequences follow directly from that. First, a liquid below the conductivity the sensor needs cannot generate a usable signal, so deionised water, pure solvents and most hydrocarbon products are out of scope rather than merely difficult. Second, the electromagnetic circuit includes the pipe and the earth, so a stable ground reference is part of the measurement, not an installation nicety. A meter that is not properly earthed will hold a drifting zero, and no amount of calibration will fix it.

What the reading is worth in service depends less on the sensor than on how it was sized and installed. A bore chosen from the pipe size alone can leave the velocity outside the working band of the sensor, and an installation close to a pump, a partly open valve or an elbow introduces swirl that the calibration did not include.

Configuration choices

Most of the specification is fixed by these decisions rather than by the accuracy class. Each one constrains the next, which is why they are settled in order.

ConfigurationOptions to fixWhat it actually decides
Liner material Elastomer and fluoropolymer families, in several grades eachChemical compatibility with the medium and the usable temperature band. This is settled first, because it constrains which electrodes are then permissible.
Electrode material Stainless steel, corrosion-resistant nickel alloys, titanium, tantalum, platinum and othersResistance to the specific medium and to abrasion. An abrasive slurry and an aggressive acid push the choice in different directions.
Liner and electrode as a pair Must be qualified together rather than chosen one at a timeA liner and an electrode can each be individually suitable and still fail as a combination against a reactive medium.
Body and installation style Flanged, wafer, insertion and hygienic variantsWhether the line has to be opened, whether a full bore section is available, and whether the process is cleaned in place.
Transmitter mounting Integral or remotely mountedWhether the value is read at a hot, vibrating or awkward point, or somewhere a person can comfortably reach.
Output and communication Pulse or frequency, 4-20 mA, HART, Modbus and other busesWhether the signal is counted as a volume, shown as an instantaneous rate, or read by a control system.
Power supply Mains, low-voltage DC or batteryWhether a supply exists at the point of installation, and whether counting has to continue through a power interruption.
Process connection standard Flange standard, pressure class and facingWhether the meter bolts onto the existing pipework or needs adapters and a second sealing interface.

How to choose an electromagnetic flow meter

FactorWhy it decides the answerHow to settle it before enquiring
Liquid conductivity Below the level the sensor needs, no stable signal can be extracted and the type is simply wrongState the fluid and its conductivity if known. Do not infer conductivity from the fluid name - the same product name covers a conductive solution and a non-conductive one.
Minimum, normal and maximum flow Sizing on the maximum alone leaves the low end of the duty in the part of the range where the reading is weakestGive all three figures, plus how many hours a day the line runs at each.
Bore and resulting velocity The velocity in the measuring section is what the sensor actually sees; the pipe size is only a starting pointState the existing pipe outside diameter and wall thickness, not the nominal size alone.
Liner and electrode pair These two determine whether the meter survives the medium at all, long before accuracy mattersList every medium the line will ever carry, including cleaning and flushing fluids.
Straight pipe run and grounding Swirl and a poor earth reference both show up as an unstable zero rather than as an obvious faultSend a sketch of the proposed location and what is immediately upstream and downstream of it.
The process environment Hygienic cleaning, washdown, a classified area and burial all change the body and enclosure, not just the labelState clean-in-place duties, the area classification, and whether the meter will be submerged or hosed down.

If any of these are still open, send what is known. A quotation can be issued against a duty description and refined once the gaps are filled.

The nearest alternatives

These are the types an enquiry for an electromagnetic flow meter usually turns out to be, and the point at which the choice is genuinely decided.

Nearest alternativeWhat separates it from a magmeter
Ultrasonic flow meters Mounted outside the pipe or inserted through it, so they need no conductive liquid and the line does not have to be opened. Clamp-on types suit retrofits and very large pipes; the reading depends on the pipe wall condition and on acoustic coupling, which a wetted magmeter does not have to care about.
Vortex flow meters A bluff body sheds alternating vortices whose frequency tracks velocity. This is the practical way to measure steam and gases, which a magmeter cannot measure at all, but it expects a clean single-phase flow and a Reynolds number inside its working band.
Coriolis mass flow meters Measures mass flow and density directly, which is what custody transfer and high-value dosing actually need. Larger bores become uneconomic and the pressure drop across the tubes may not suit a gravity-fed line.
Turbine and positive displacement meters Mechanical counting of a rotating or displacing element, well suited to clean low-viscosity liquids and to batch dispensing. Solids, fibres and abrasion are what rule them out where a magmeter keeps working.
Open channel flow meters For flow in a channel with a free surface, where depth is converted to a rate through a known structure. A magmeter requires the pipe to run full, so this is the answer where there is no pressurised pipe to measure in.
Variable area flow meters A float rises in a tapered tube to give a visual indication without power. Simple and cheap to install, but local-reading only and ill-suited to opaque, dirty or automated duties.

Two of these alternatives cannot be used on steam or gas flow at all, and the magmeter is one of them. Where the same line carries both liquid and gas duties, that alone decides the technology.

What to include in the enquiry

The first reply can be a quotation rather than a set of questions if the enquiry carries these. Where a figure is not known, send the duty description and we will confirm what it implies.

  1. Medium name, composition, and conductivity where it is known
  2. Minimum, normal and maximum flow rate
  3. Pipe outside diameter and wall thickness, and the flange standard it must match
  4. Liner and electrode preference, or the chemical environment if that is not yet decided
  5. Range of medium temperature and line pressure in service
  6. Output required, and what will read it
  7. Power available at the point of installation, and whether a remote display is needed
  8. Whether the process is cleaned in place, and whether the area is classified as hazardous
  9. Quantity, destination port and required delivery date

Available products

1 model in Electromagnetic Flow Meters

White-bodied flow meter with a red transmitter housing, an integral display reading 13.625 m³/h and a running total, three buttons marked ESC, ENT and a direction key below the display, two cable glands on the side, and a red flow-direction arrow moulded on the white measuring section between two flanges

LDG-SUP · Electromagnetic Flow Meters

Intelligent Electromagnetic Flow Meter

A direct-display electromagnetic flow meter for conductive liquids, from DN10 to DN2000, with the liner and electrode selected against the medium and its temperature.

Model
LDG-SUP
Media
Conductive liquids at ≥50 µS/cm, including water, wastewater, coolant, paper stock and acid or alkali solutions; ≥2 µS/cm for the liquid-cooling form and ≥5 µS/cm for the slurry form
Nominal size
DN10 to DN2000 standard, DN6 to DN65 micro-bore, DN300 to DN2200 to order
Accuracy
±0.5 % of reading

Also in Flow Measurement

Other product types in this category

Every type we quote for under Flow Measurement. A type with no link yet is still quoted for - it is described on the Flow Measurement overview, and gets a page of its own as soon as a model is published against it.

Frequently asked

Electromagnetic Flow Meters questions

Can an electromagnetic flow meter measure a liquid that does not conduct electricity?

No. The signal is generated by the liquid moving through a magnetic field, so a medium that will not carry the tiny induced current produces nothing to measure. Deionised water, pure solvents, oils and most refined hydrocarbons fall outside the type. Those duties go to an ultrasonic, turbine, positive displacement or Coriolis meter instead.

Does it work on gas or steam?

No. Gases are not conductive, so the principle does not apply. Steam and gas flow are normally handled by vortex, thermal mass or Coriolis instruments. If a single line alternates between a conductive liquid and a gas, that alternation has to be settled before the flow technology is chosen, because no single one of these covers both.

Why is earthing treated as part of the measurement rather than part of the wiring?

The circuit that carries the signal includes the liquid, the pipe and the earth. If the pipeline is not at a stable potential, the meter cannot distinguish the induced signal from the potential difference, and the zero drifts. Grounding rings and a proper earth connection are what keep the measurement reference stable, which is why they appear on the quotation rather than in a footnote.

Can a magmeter be fitted without shutting the line down?

The flanged and wafer bodies are normally fitted into an opened line. An insertion version can in some cases be installed through a valve on a live pipe, but whether that is acceptable depends on the medium, the pressure and the site procedure, so it has to be confirmed against the actual line rather than assumed.

Quoting for Electromagnetic Flow Meters

Send the specification and we will confirm the matching model, availability and lead time. Minimum order quantity is 1 pc.

Request for quotation

Request a quotation - Electromagnetic Flow Meters

Send the technical detail and we will confirm availability, lead time and terms. In-stock items ship within 48 hours; customized specifications typically take 2-10 days. Minimum order quantity is 1 pc.

The more of this you can give us, the fewer exchanges are needed before we can quote.
No file chosen
Datasheet, drawing, BOM or photograph. One file, up to 10 MB (PDF, Office, image or ZIP).

By submitting this form you agree that we may contact you about this enquiry. We do not sell or share enquiry data. See our privacy policy.

Items held in stock are dispatched within 48 hours of order confirmation. Customized specifications are produced to order and typically ship within 2 to 10 days. Transit time then depends on the shipping method and destination.

Request a Quote WhatsApp