Product type

Vortex Flow Meters

A vortex flow meter measures flow by counting the vortices shed behind a bluff body placed in the stream. Each vortex arrives as a pressure pulse, and the frequency at which the pulses arrive is proportional to velocity over a wide band, so the instrument turns a mechanical rhythm into a flow rate without any moving part. Because the body sits in the line and the electronics count a frequency rather than read a displacement, the type tolerates temperature and pressure that would shorten the life of a mechanical meter.

What a vortex flow meter is

A vortex flow meter measures flow by counting the vortices shed behind a bluff body placed in the stream. Each vortex arrives as a pressure pulse, and the frequency at which the pulses arrive is proportional to velocity over a wide band, so the instrument turns a mechanical rhythm into a flow rate without any moving part. Because the body sits in the line and the electronics count a frequency rather than read a displacement, the type tolerates temperature and pressure that would shorten the life of a mechanical meter.

That is why it is the common answer for steam. Saturated steam, superheated steam, compressed air, nitrogen and most process gases are measured with a vortex meter wherever the line is a clean single-phase stream, and the same instrument will measure low-viscosity liquids such as water and condensate. Where a plant meters a boiler header, a dyehouse or a compressor house, it is usually this type doing the metering.

This page covers how one is configured: what the body, the bore and the process connection are being asked to survive, when temperature and pressure compensation has to be added before the figure means anything, and which of the neighbouring flow technologies takes over when the medium is not a clean single-phase stream.

How a vortex flow meter measures

The bluff body is a deliberately unstreamlined obstruction. As the stream passes it, vortices are shed alternately from the two sides, and each shed vortex removes a small packet of pressure from the edge behind it; a sensor in the body detects the alternation as a frequency. Across the band of Reynolds numbers the type is designed for, that frequency is proportional to velocity, so the meter converts it into a volumetric rate using the bore area. The proportionality belongs to the geometry of the body rather than to the particular gas, which is why one body can be offered for several media.

Three consequences follow. The meter needs a single-phase stream, because a vortex shed by a liquid is disturbed by droplets and a vortex shed by a gas is disturbed by condensate, so wet steam and two-phase flow are outside the type. It needs a velocity inside its band, because at the low end the shedding stops being regular and at the high end erosion of the body sets the ceiling. And it needs a settled, swirl-free profile at the body, because the frequency is a velocity measurement in disguise and any disturbance upstream is read as a change in flow.

The signal being a frequency is the practical reason the type survives conditions that defeat others: a frequency does not drift the way an analogue span does. What it is not immune to is the medium changing state inside the meter, which is why a steam duty is normally paired with compensation rather than measured raw.

Configuration choices

Most of the specification is fixed by these decisions rather than by the accuracy class. Each one constrains the next, which is why they are settled in order.

ConfigurationOptions to fixWhat it actually decides
Bore and body style Flanged, wafer and insertion variants across a range of nominal sizesWhether the line has to be opened for a full-bore body or can take an insertion type, and whether the velocity at the duty falls inside the band the body works in.
Body and wetted material Carbon steel and stainless steel as the common starting pointsWhether the body survives the medium and the temperature, which is settled before accuracy is discussed at all.
Medium family Steam, gas or liquid, which the meter is ordered for rather than changed afterwardsThe calibration and the compensation arrangement. The same body measured raw is a different instrument from the same body compensated for steam.
Temperature and pressure compensation Standard, temperature only, pressure only, or both, in an integral or a separate arrangementWhether the output is a true mass or standard-volume figure or only a volumetric one. A gas or steam figure without compensation is a volume at line conditions, which is not what most accounting needs.
Output and communication Pulse, current, serial and HART optionsWhether the signal is counted as a total, shown as a rate, or read by a control system.
Power supply Loop-powered from low-voltage DC, or from an internal batteryWhether a supply exists at the point of installation, and how long the instrument can be left unattended.
Process connection and flange standard The flange standard, pressure class and facing of the existing pipeworkWhether the meter bolts on directly or needs adapters and a second sealing interface.
Ambient duty and mounting Vibration level, insulation, and whether the head has to be reached for readingWhether a heavier body is warranted, and how the enclosure is oriented, since a head sitting above a hot line ages faster than one set to the side.

How to choose a vortex flow meter

FactorWhy it decides the answerHow to settle it before enquiring
Whether the stream is single phase Wet steam, entrained droplets and two-phase mixtures disturb the vortex and the reading with itState whether the steam is dry and whether a separator exists upstream, and whether the gas can condense in the line.
Minimum, normal and maximum flow The low end decides the bore, not the maximum, because a bore sized on the peak leaves the normal duty at the bottom of the bandGive all three figures, and the hours a day each applies.
Medium temperature and pressure These decide the body rating and, for steam and gas, whether compensation is required before the figure means anythingState the working figures as well as the design figures, and whether the condition varies.
Pipe size and the velocity it implies The body is chosen so the duty sits inside the working band, which may mean a bore different from the pipeGive the pipe outside diameter and wall thickness, not the nominal size alone.
Straight pipe run available Swirl from an elbow, a partly open valve or a reducer is read as a change in flowSend a sketch of what is immediately upstream and downstream of the proposed point.
Vibration at the point Pipe vibration at the shedding frequency is indistinguishable from flowDescribe the line and what it is attached to, and whether the meter can be moved.

If any of these are still open, send what is known. A quotation can be issued against a duty description and refined once the gaps are filled.

The nearest alternatives

These are the types an enquiry for a vortex flow meter usually turns out to be, and the point at which the choice is genuinely decided.

Nearest alternativeWhat separates it from a vortex meter
Electromagnetic flow meters Sits wetted in the line and measures only conductive liquids. It cannot measure steam or gas at all, which is usually the duty a vortex meter is bought for; conversely it does not care whether the liquid is clean, so slurry and dirty water go to it rather than to a body that would erode.
Ultrasonic flow meters Mounted outside the pipe or inserted through it, so the line need not be opened and the medium need not be conductive. Clamp-on types suit retrofits and large existing mains, but their reading depends on the pipe wall and the acoustic coupling, and they are not the usual answer for steam.
Thermal mass flow meters Reads gas flow from heat transfer at low velocities, which is exactly where a vortex body stops shedding reliably. It is a gas-only instrument and it reads mass rather than volume.
Turbine flow meters Counts a rotating element in the stream, accurate on clean low-viscosity liquids and widely used for batch dispensing. Bearings and blades are what make it intolerant of steam, dirt and dry gas.
Variable area flow meters Gives a local visual indication without power, simple and inexpensive on small purge and utility lines. Ill-suited to opaque media, to totals, and to anything read remotely.
Coriolis mass flow meters Measures mass flow and density directly, which is what custody transfer and high-value dosing actually need. Pressure drop and cost both rise steeply with bore, so it is not the general answer for a large steam header.

The vortex meter and the thermal mass meter are the two types that measure gas without a moving part; the boundary between them is velocity rather than medium.

What to include in the enquiry

The first reply can be a quotation rather than a set of questions if the enquiry carries these. Where a figure is not known, send the duty description and we will confirm what it implies.

  1. The medium, and whether it is steam, gas or liquid, and whether the steam is dry
  2. Minimum, normal and maximum flow, with the hours a day each applies
  3. Medium temperature and pressure in service, and whether they vary
  4. Pipe outside diameter, wall thickness and the flange standard it must match
  5. Whether the figure required is a volume at line conditions or a compensated mass or standard volume
  6. Output required, and what will read it
  7. Power available at the point of installation
  8. Straight pipe run available upstream and downstream
  9. Ambient conditions, including vibration and whether the line is insulated
  10. Quantity, destination port and required delivery date

Available products

1 model in Vortex Flow Meters

Flow meter head with a blue casing, a dark liquid-crystal display and three buttons beneath it, carried on a stainless steel stem above a flanged pipe body with a large flange at each end, a separate armoured temperature probe on a flexible conduit beside it, and a small red flow-direction label on the body

LUGB-SUP (2 models) · Vortex Flow Meters

Vortex Steam Flow Meter

A vortex flow meter for steam, gas and liquid lines, supplied in an integral and a conventional form with pulse, current or serial output and optional temperature and pressure compensation.

Model
LUGB-SUP / LUGB-SUP-C
Media
Liquid, gas and steam, including saturated and superheated steam
Nominal size
DN15 to DN300 as a full-bore body; DN300 to DN1000 as an insertion type
Accuracy
1.0 % to 2.5 % of reading, according to medium, size and compensation

Also in Flow Measurement

Other product types in this category

Every type we quote for under Flow Measurement. A type with no link yet is still quoted for - it is described on the Flow Measurement overview, and gets a page of its own as soon as a model is published against it.

Frequently asked

Vortex Flow Meters questions

Can a vortex flow meter measure wet steam?

No, not reliably, and this is the single most common mistake with the type. The instrument counts vortices shed from a bluff body, so it needs a single-phase stream at the body. Droplets carried in wet steam disturb the shedding and the reading drifts or drops out, and the usual remedy is a separator upstream rather than a different meter. The same applies to a gas that can condense inside the meter, which is why the line and the instrument are checked against the dew point as well as against the working pressure.

Why is temperature and pressure compensation offered as a separate decision?

Because a vortex meter measures volume, not mass. Without compensation what it produces is the volume flowing at the actual line conditions, and for a gas or steam duty that figure changes whenever the pressure or the temperature changes, even when the same amount of energy is being delivered. Adding compensation lets the instrument convert the reading to a standard volume or a mass, which is normally what an energy account needs. Whether it is required is a question about the duty, not about the meter.

How much straight pipe does it need?

The body has to see a settled, swirl-free profile, so a straight run is required upstream and downstream of it, the upstream figure being the larger of the two. Any disturbance close to the meter, such as an elbow, a partly open valve, a reducer or a thermowell, is read as a change in flow and appears as an error that calibration cannot correct. Where the space available is shorter than the run requires, that has to be settled before the meter is ordered rather than after.

What decides the low end of the range?

Velocity at the body. The frequency being counted is proportional to velocity, and below a certain velocity the vortices stop being shed regularly enough to count, so the low end is set by the physics of the body rather than by an electronic limit. It is the reason a bore is chosen so the normal duty sits in the middle of the band rather than at the bottom, and the reason a pipe oversized for its flow makes a poor vortex installation.

Quoting for Vortex Flow Meters

Send the specification and we will confirm the matching model, availability and lead time. Minimum order quantity is 1 pc.

Request for quotation

Request a quotation - Vortex Flow Meters

Send the technical detail and we will confirm availability, lead time and terms. In-stock items ship within 48 hours; customized specifications typically take 2-10 days. Minimum order quantity is 1 pc.

The more of this you can give us, the fewer exchanges are needed before we can quote.
No file chosen
Datasheet, drawing, BOM or photograph. One file, up to 10 MB (PDF, Office, image or ZIP).

By submitting this form you agree that we may contact you about this enquiry. We do not sell or share enquiry data. See our privacy policy.

Items held in stock are dispatched within 48 hours of order confirmation. Customized specifications are produced to order and typically ship within 2 to 10 days. Transit time then depends on the shipping method and destination.

Request a Quote WhatsApp