- Model
- Fourteen models across three series, from MIK-RD908 to MIK-RD702
- Series
- 80 GHz high-frequency, low-frequency, and guided-wave
- Range
- 0 to 10 m through to 0 to 80 m, according to series and model
- Accuracy
- ±5 mm on the shortest spans through to ±30 mm at a 70 m span
- Frequency
- 80 GHz frequency-modulated continuous wave on the high-frequency series; 500 MHz to 1.8 GHz on the guided-wave series
- Beam angle
- 3° to 10° on the high-frequency series, and as narrow as 3°
- Protection
- IP65, IP67 or IP68 according to model
- Outputs
- 4-20 mA with HART, and RS-485 with Modbus on the high-frequency series
- Process pressure
- -0.1 to 0.3 MPa through to -0.1 to 4 MPa, according to model
- Process temperature
- -40 to 250 °C on the guided-wave series
Radar is the level technology that works when the surface cannot be seen. It measures with microwaves rather than with sound, so vapour, steam, a temperature layer, dust and foam that would disturb an acoustic pulse pass through it largely unaffected. That is why it is the answer for a hot process vessel, a dusty silo and an outdoor river gauge, and why it is normally the more expensive of the two non-contact options.
The range behind this page carries that principle across three different antenna arrangements, because what changes between duties is not the idea but how the signal is delivered.
What the three series are for
The high-frequency series radiates at 80 GHz, which is a short enough wavelength to resolve small targets and to be focused into a narrow beam. That combination is what makes it usable on a tall silo where the surface is far away, and on a vessel with an obstruction close to the antenna which a wider beam would strike and read instead of the surface. The narrowest beam in the range is given as 3°, and one model reaches a blanking distance of 8 cm, which is what allows measurement to continue close beneath the instrument.
The low-frequency series uses far larger antennas for the same job and is described for liquids in tanks, including strongly corrosive ones where the antenna material has to be chosen against the medium. The guided-wave series abandons free-space radiation altogether: the signal runs along a rod or a cable that reaches down into the liquid, so the path is fixed and the problems that afflict a beam in open air disappear with the beam. It is the series that reaches the highest process temperature in the range.
Choosing between them
The first question is not range but path. A free-space instrument needs a clear line from its antenna to the surface, so if there is foam, heavy condensation, a narrow vessel, an agitator in the beam or a process hot enough to trouble the antenna, the answer is the guided-wave series. Where the path is clear, the choice between high and low frequency is mostly one of distance and target size: the high-frequency series resolves smaller targets and can be aimed more precisely, which matters on a tall or obstructed vessel, and the low-frequency series is the simpler route where the surface is close and the beam has room.
Range and accuracy then narrow the model rather than the series, and both are given per model in the material because the antenna and the medium change what is achievable. The general description also claims an accuracy of 0.1 %, which is a different figure from the per-model millimetre values and is not reconciled with them; the per-model figures are the ones to work from.
Process conditions and the wetted parts
Pressure and temperature decide the model more often than the range does. Across the range, pressure spans from a reference to atmosphere on the models intended for open vessels up to 4 MPa on those built for pressurised service, and temperature from ambient on the 80 GHz models to 250 °C on the guided-wave series. A process vessel with both pressure and temperature on it therefore has a shorter list of candidates than its level range alone would suggest.
The wetted parts follow the medium. Antennas are offered in rod, horn, cable and sealed corrosion-resistant forms, and the flange and horn on the high-frequency series are stainless steel. Where the medium is aggressive, the antenna material and the sealing around it are what decide whether the instrument survives, and the material offers a corrosion-resistant antenna form for exactly that case.
Installation and the two errors to avoid
Two errors account for most radar installations that do not work, and the material states both. The first is a level that rises into the blanking distance: close to the antenna the instrument cannot separate its own transmission from the returning echo, so the highest level the vessel may reach has to stay below that band. The second is an obstruction inside the beam. The signal is radiated in a cone, and anything within that cone - a filling pipe, a ladder, a heating coil, the vessel wall on a narrow vessel - returns an echo that may arrive before the surface echo does. The material’s instruction is accordingly to keep the beam clear and to set the antenna face square to the surface, with the reference plane taken at the underside of the thread or the flange sealing face.
Measurement limitations and selection considerations
The limitations belong to the technology rather than to the range. Radar measures to the first strong reflection in its beam, so a foam layer can be read as the surface if it is dense enough, and a very low dielectric medium reflects weakly and may return too little to resolve. Neither is a fault - they are the conditions under which another principle is the better answer, which is why the boundary between radar and ultrasonic is drawn by the atmosphere above the medium and the boundary between radar and a wetted probe is drawn by what is in the vessel.
The material also leaves a number of figures unsettled, and they are listed rather than glossed. The protection rating varies by model, the supply voltage is stated for two models only, the process temperature is absent for most of the low-frequency and high-frequency series, and one model is given two different ranges in different places in the same document. Those are recorded as questions rather than resolved here, because settling them by inference would put an unverified figure on a specification sheet.
Ordering
The items that fix the answer are the vessel height, diameter and the highest and lowest levels; the medium and whether it is a liquid, a powder or a solid; the vapour, dust, foam and condensation above the surface; the process pressure and temperature; what is inside the vessel and how much clearance the antenna has to the wall; the process connection the vessel provides; the outputs required and what will read them; and whether the reading has to be visible at the vessel or only as a signal. A vessel drawing with pressure and temperature marked on it answers most of these, and it is the most useful single item in an enquiry. Quantity, destination port and required delivery date complete it.
Every value below is taken from source documentation. Where a parameter is not stated in the available material it is marked as information required rather than estimated.