- Resistance at 25°C
- 10 kΩ, ±1%
- B constant B25/50
- 3950 K, ±1%
- Thermal time constant
- 3 s, measured in stirred water from 25 to 50°C
- Operating temperature
- -30 to 180°C in the parameter table; -20 to 105°C on the main image
- Dissipation constant
- 3.6 mW/°C in still air
- Maximum power
- 256 mW at 25°C in still air
- Dielectric strength
- AC1800 V for 1 s, or AC1500 V for 1 min, in water at 1 mA
- Insulation resistance
- ≥100 MΩ at DC 500 V
- Probe
- 304 stainless steel, 5×25 mm
- Resistance options
- 5K, 10K, 50K and 100K
An NTC thermistor temperature probe measures temperature through a semiconductor element whose resistance falls as it warms. That behaviour is the opposite of the platinum elements used in process RTDs, and it is why this family is specified by its own pair of numbers rather than by a Pt designation: the resistance at a reference temperature, and the B constant that describes how steeply the resistance changes across the range.
The build on this page is the 10K variant, with a nominal 10 kΩ at 25°C and a B25/50 value of 3950 K, both held to ±1%. The sensing element sits in a 304 stainless steel probe of 5×25 mm, brought out on lead wires and terminated in XH-2P plug connectors so the probe can be plugged straight into a control board or an acquisition module rather than landed on a terminal block.
Because the 25°C resistance and the B constant are both toleranced, the two figures a control board needs in order to linearise the signal are specified rather than nominal. That is the practical difference between a probe that tracks a setpoint in a thermostatic appliance and one that merely switches near it.
How an NTC thermistor sensor works
A thermistor is a semiconductor whose carrier concentration changes with temperature, and for a negative temperature coefficient element the resistance drops as the element warms. The change is steep compared with a metal element, which is the source of both its strengths and its limits. Over a narrow span around room temperature a thermistor produces a large resistance change for a small temperature change, so a simple circuit can resolve a fine increment. Over a wide span the same curve is strongly non-linear, so the reading has to be linearised against the specific element, which is exactly what the R25 and B pair describe.
That is why two probes with the same nominal resistance are not interchangeable. Two 10 kΩ elements with different B constants follow different curves, and a board linearised for one will read offset from the other across the range even though both agree at 25°C. The material supplied here states the B value for the 10K build only and leaves the other resistance options without one, so those options cannot be treated as the same device with a different reference resistance.
The probe body and how it meets the medium set what the element actually sees. A stainless sheath gives the element mechanical protection and a defined thermal path, and the thermal time constant of 3 seconds measured in stirred water is a property of that assembly rather than of the semiconductor alone: sheath diameter and wall thickness, and how firmly the element sits inside it, matter more than the element type. The same probe in still air is a slower device, and the material states as much by measuring the constant in agitated water.
Self-heating is the second effect to keep in view. The dissipation constant of 3.6 mW/°C is the power that raises the sensing body by 1°C in still air, and the 256 mW maximum power is a destruction limit rather than a working figure. Between them sits the design decision: enough excitation current to resolve the temperature, not so much that the element warms itself. In still air, where heat leaves slowly, that ceiling is much lower than it is in a liquid.
How to select the right NTC probe
Start from what the reading has to drive. A thermostat, a protection cut-out and a temperature display all place different demands on the same probe, and the two numbers that decide whether a board can use it are the resistance at 25°C and the B constant. Where a board is already built for one pair, changing either the resistance value or the B value changes the displayed temperature, so the probe has to be matched to the input rather than bought to the same nominal value.
Then the temperature span. The two ranges stated in the supplied material do not agree, and the material itself flags the discrepancy, so a hot application should be engineered against the lower figure until that is confirmed. A probe chosen near the top of a range leaves no margin for the tolerance on the element or for the difference between the medium temperature and the temperature at the element.
Then the mechanical fit. The standard probe is 5×25 mm and the material offers other dimensions to order, but probe size is not only a fitting question: a larger sheath responds more slowly, and a smaller one reaches into places a larger one cannot. Where the probe is pressed against a surface rather than immersed, the contact area and the clamping force decide the reading as much as the element does.
Finally the connection. The XH-2P plug suits a board with a mating header. Where the run is long or the environment is wet, the lead length and its insulation have to be settled, and neither is stated in the supplied material.
Limitations and points to confirm
The element family is the first limitation. This is a thermistor, not a platinum RTD, so it cannot be substituted onto a PT100 input and it cannot be used where a documented, traceable temperature is required without an R-T table and a calibration record. Where the process needs a temperature that can be referred back to a standard, the platinum family is the one to use and this probe is not an equivalent.
The second is that the supplied material gives no resistance-temperature table. The R25 and B pair describes the curve, but a control board is usually linearised against a table rather than against two figures, and several of the reliability tests are stated as a permitted drift on resistance, which can only be converted into a temperature error once that table is available.
Third, the material states no ingress protection rating, no lead length, no lead temperature rating and no certification. Those are published on this page as information required rather than estimated. The dielectric strength and insulation resistance figures were measured in water, which speaks to the electrical isolation of the lead assembly, but they are not a statement about how long the probe may remain immersed or in what media.
Finally, the identification is open. The product carries no model designation in the supplied material, so where an order is placed the resistance value, the B value, the probe dimensions, the lead length and the terminal form all need to be stated rather than quoted as a code.
Every value below is taken from source documentation. Where a parameter is not stated in the available material it is marked as information required rather than estimated.