Level Measurement · Vibrating Fork Level Switches

Vibrating Fork Level Switch

A vibrating fork level switch for point level in tanks and pipes, rated to 2 MPa with a fork temperature of -30 to 150 °C, in relay, transistor or CAN output and 24 V DC or 220 V AC supply.

QDY30A-SX ·

Key specifications

Model
QDY30A-SX
Pressure rating
2 MPa
Fork temperature
-30 to 150 °C, with higher temperatures to order
Ambient temperature
-20 to 70 °C at the housing
Output
Relay SPDT or DPDT, one PNP and one NPN transistor output, or CAN
Supply
24 V DC or 220 V AC
Process connection
G1/2A thread as standard, with flanged versions
Wetted material
Stainless steel, with a PTFE-coated option

A level transmitter answers how much is in the tank. A level switch answers whether the level has reached a point, and for a pump cut-out, a high-level alarm or a dry-run protection that is the only question being asked.

The vibrating fork is the switch type that has no moving part to jam and no gap for a coating to bridge, which is why it is the usual choice for slurries, viscous liquids and solids that would defeat a float.

Product overview

The switch is a stainless fork on a threaded or flanged body, with the electronics in the housing above it. The material gives a 2 MPa pressure rating, a fork temperature of -30 to 150 °C with higher temperatures to order, and an ambient limit of -20 to 70 °C at the housing.

Output is a relay, a PNP and NPN transistor pair, or CAN, depending on the form; supply is 24 V DC or 220 V AC. The process connection is G1/2A as standard, with flanged versions, and a PTFE-coated fork is offered for aggressive media.

How a vibrating fork switch works

The fork vibrates at its resonant frequency in air. When the medium covers it, the added mass changes that frequency, and the electronics detect the shift and change the state of the output.

That mechanism explains most of the practical behaviour. There is no float to stick and no gap for solids to bridge, so a slurry that would jam a float switch passes the fork without effect. The switch does not need calibration to a level, because it is not measuring level; it is detecting whether the fork is covered. And it needs a minimum density to work, because a medium too light to shift the frequency will not be detected — which is the one figure the material does not give.

How to select the right switch

Medium and density. The first question is what the fork will sit in and whether it is heavy enough to shift the frequency. Water, slurries and most process liquids are well inside the range; light powders, foams and aerated media are the cases to check.

Pressure and temperature at the nozzle. The 2 MPa rating and the -30 to 150 °C fork range cover most tanks and lines. Above 150 °C the material offers a higher-temperature construction to order, and the housing stays within its own ambient limit because of the heat-break section between the fork and the electronics.

Output. A relay drives a contactor or an alarm directly. A PNP/NPN pair suits a PLC input. CAN suits a plant that already carries a bus. The choice is decided by what the signal is connected to, not by the switch.

Connection and insertion length. G1/2A is the standard thread; a flange is used where the nozzle is larger or the vessel is classified. The insertion length follows the nozzle depth, and the nozzle drawing is more use than the pipe size.

Installation and configuration

The switch is screwed or bolted into the nozzle, with the fork at the level to be detected. The material requires the cable entry to face downwards and the gland to be tightened, which is the ordinary precaution against water running down the cable into the housing.

The fork should sit clear of the nozzle wall and clear of the inlet stream, so that a falling stream or a build-up on the wall does not cover it. The material gives no minimum clearance and no insertion depth, and neither is invented here.

Measurement limitations and selection considerations

The first limitation is density. A medium too light to shift the fork frequency will not be detected, and the material does not state the threshold, so a sample should be checked before the order.

The second is build-up. A coating that bridges the two tines damps the vibration and can hold the switch in one state; the PTFE-coated form is the answer for media that tend to adhere, but it is a mitigation rather than a cure.

The third is that the switch gives no warning of drift. It is a contact, not a measurement, so a failed switch is usually found when the pump runs dry or the tank overflows. Testing the output at commissioning, and recording the state with the fork covered and uncovered, is worth more than any figure on the datasheet.

Features

  • A switching output rather than a continuous reading, which is what a pump cut-out or a high-level alarm actually needs
  • Relay, transistor and CAN output forms, so the switch can drive a contactor, a PLC input or a bus segment without an interface relay
  • A fork temperature of -30 to 150 °C with higher temperatures to order, covering hot process lines as well as ambient tanks
  • Stainless steel forks with a PTFE coating for aggressive media, and a form described for high-viscosity and solids-bearing liquids
  • A G1/2A thread as standard, with flanged versions for larger nozzles
  • An explosion-proof form in the range, for classified areas

Technical specifications

Every value below is taken from source documentation. Where a parameter is not stated in the available material it is marked as information required rather than estimated.

Measurement
FunctionPoint level: the switch changes state when the fork is covered, and changes back when it is uncoveredStandard
Pressure rating2 MPaStandard
Fork temperature-30 to 150 °C, with a higher temperature to orderStandard
Ambient temperature-20 to 70 °C at the housingStandard
Repeatability0.2 % is quoted on one listing and 2 % on another; the two are not the same quantity and neither is resolved hereInformation required
Medium densityThe material refers to a minimum density but does not give the figureInformation required
Viscosity limitNot stated in the material, although high-viscosity and solids-bearing media are named as dutiesInformation required
Switching delayNot stated in the materialInformation required
Output and supply
Relay outputSPDT or DPDT, depending on the formStandard
Transistor outputOne PNP and one NPN output on the form that carries themStandard
Serial outputCAN on the form that carries itStandard
Supply24 V DC or 220 V AC, depending on the formStandard
Fail-safe directionNot stated in the materialInformation required
Mechanical
Process connectionG1/2A thread as standard, with flanged versions; the cable entry is M12 x 1 on the form that uses a connectorStandard
Fork and body materialStainless steel, with a PTFE coating for aggressive mediaStandard
Insertion lengthNot stated in the materialInformation required
Ingress protectionNot stated in the materialInformation required
WeightNot stated in the materialInformation required
Environment
Hazardous areaAn explosion-proof form is listed; the marking and certificate are not statedInformation required
Cable entry orientationThe material requires the entry to face downwards and the gland to be tightenedStandard

Available models

Selection table
Model Configuration Key ranges Availability
QDY30A-SX, relay SPDT Single changeover contact, 24 V DC or 220 V AC supply 2 MPa; -30 to 150 °C fork; G1/2A thread The general form for a pump cut-out or an alarm
QDY30A-SX, relay DPDT Two changeover contacts for two independent circuits Same pressure and temperature Used where the switch has to drive an alarm and a pump starter separately
QDY30A-SX, PNP and NPN One PNP and one NPN transistor output for a PLC input Same pressure and temperature For a control system rather than a contactor
QDY30A-SX, CAN Serial output on a bus segment Same pressure and temperature For a plant that already carries a CAN network
High-temperature form Fork and housing arranged for a higher medium temperature Above 150 °C to order Quoted against the duty rather than held as a stock range

Customization

  • Process connection, from a G1/2A thread to a flange matched to the nozzle
  • Fork length, where the nozzle depth requires a longer insertion
  • Material, as stainless steel or a PTFE-coated fork for aggressive media
  • Output, as a relay, a transistor pair or CAN
  • Supply, as 24 V DC or 220 V AC
  • High-temperature construction for media above 150 °C

Certification and compliance

Certification documents not yet supplied

Certifications are only published once a certificate copy can be produced, so this section is deliberately empty rather than populated with assumed approvals. Tell us which approvals your application requires and we will confirm what is available for this instrument.

Parameters still to be confirmed

The following are required for a complete specification but are not stated in the documentation supplied to us. They are listed rather than estimated:

  • The minimum medium density the fork needs to switch
  • The viscosity limit, although high-viscosity media are named as duties
  • The ingress protection rating of the housing
  • The insertion length of each form and the fork length available
  • The switching delay and the fail-safe direction
  • The relay contact rating and the transistor load
  • The explosion-proof marking and the certificate that covers it
  • The repeatability basis, since 0.2 % and 2 % both appear
  • The weight
  • The higher fork temperature that can be ordered
  • Warranty period and the terms that apply

Frequently asked questions

What has to be confirmed before a vibrating fork switch can be quoted?

The medium and its minimum density, because a fork that vibrates freely in water may not shift enough in a light powder or a foam. Then the pressure and temperature at the nozzle, the process connection and its thread or flange standard, the output the control system needs, and the supply available on site. The insertion length follows from the nozzle depth, and it is worth giving the nozzle drawing rather than the pipe size alone.

How is this different from a level transmitter?

A transmitter reads the level continuously and gives a number over its whole range; a switch changes state at one point and gives a contact. A pump cut-out, a high-level alarm and a dry-run protection are switch duties, and a switch is the simpler and more robust choice for them. A transmitter is the right instrument when the level itself has to be known, not only whether it has passed a point.

Will it work in a viscous or solids-bearing liquid?

The material names high-viscosity liquids, liquids with suspended solids and slurries as duties, which is the usual reason a fork is chosen over a float or a capacitive probe: there is no moving part to jam and no gap for a coating to bridge. The viscosity limit and the minimum density are not given, though, so a sample of the medium and its density should be confirmed before the order rather than after.

What does the heat-break section do?

It separates the fork, which sits at the medium temperature, from the housing, which carries the electronics and is rated to 70 °C ambient. On a hot line the fork can be at 150 °C, and without that separation the housing would run above its own limit. It is the reason the switch can be used on a hot process without a cooling extension.

Related products

Other models in the same range

Stainless steel cylindrical probe with a black end cap carrying a central pressure port and a ring of four smaller ports around it, joined to a coiled length of black cable with two bare conductors emerging at the far end

XK-136P · Hydrostatic Level Transmitters

Submersible Level Transmitter

Submersible hydrostatic level transmitter for water tanks, sumps, reservoirs and pits, from 1 m to 10 m as standard, with a probe rated IP68.

Model
XK-136P
Type
Submersible hydrostatic level transmitter with a vented cable
Range
0 to 1 m, 0 to 3 m, 0 to 5 m and 0 to 10 m as standard, to 500 m to order
Accuracy
0.5 class, with 0.2 class to order
Integrated ultrasonic level meter standing upright with a translucent red top section, a grey threaded ring below it, a white body carrying two screened circular fittings on the front and the letters DC moulded beneath them, and a black lower section ending in the transducer face

SIN-MP-C (4 models) · Ultrasonic Level Meters

Ultrasonic Level Meter

Non-contact ultrasonic level meter for tanks, sumps, channels and silos, in integral and separate forms, with 4-20 mA and RS-485 outputs and a relay pair.

Model
SIN-MP-C / SIN-ULS-B / SIN-WSU100 / WSU200
Mounting
Non-contact, above the medium
Forms
Integral, with the transducer in the head, or separate, with the head and probe mounted apart
Range
0 to 1 m through to 0 to 15 m across the forms
Radar level meter with a blue cap over a stainless cylindrical housing carrying two cable entries and a cover screw, a black nameplate on the body, and a large stainless flange at the base drilled for bolts with a raised sealing face in the centre

MIK-RD908 (3 models) · Radar Level Meters

80 GHz Radar Level Meter

Radar level meter in 80 GHz, low-frequency and guided-wave series for tanks, silos, rivers and pressurised vessels, with spans from 10 m to 80 m.

Model
Fourteen models across three series, from MIK-RD908 to MIK-RD702
Series
80 GHz high-frequency, low-frequency, and guided-wave
Range
0 to 10 m through to 0 to 80 m, according to series and model
Accuracy
±5 mm on the shortest spans through to ±30 mm at a 70 m span

Request a quotation for the QDY30A-SX

Send the configuration you need and we will confirm availability, lead time and terms. Minimum order quantity is 1 pc.

Request for quotation

Request a quotation - QDY30A-SX

Send the technical detail and we will confirm availability, lead time and terms. In-stock items ship within 48 hours; customized specifications typically take 2-10 days. Minimum order quantity is 1 pc.

The more of this you can give us, the fewer exchanges are needed before we can quote.
No file chosen
Datasheet, drawing, BOM or photograph. One file, up to 10 MB (PDF, Office, image or ZIP).

By submitting this form you agree that we may contact you about this enquiry. We do not sell or share enquiry data. See our privacy policy.

Items held in stock are dispatched within 48 hours of order confirmation. Customized specifications are produced to order and typically ship within 2 to 10 days. Transit time then depends on the shipping method and destination.

Request a Quote WhatsApp