A level transmitter answers how much is in the tank. A level switch answers whether the level has reached a point, and for a pump cut-out, a high-level alarm or a dry-run protection that is the only question being asked.
The vibrating fork is the switch type that has no moving part to jam and no gap for a coating to bridge, which is why it is the usual choice for slurries, viscous liquids and solids that would defeat a float.
Product overview
The switch is a stainless fork on a threaded or flanged body, with the electronics in the housing above it. The material gives a 2 MPa pressure rating, a fork temperature of -30 to 150 °C with higher temperatures to order, and an ambient limit of -20 to 70 °C at the housing.
Output is a relay, a PNP and NPN transistor pair, or CAN, depending on the form; supply is 24 V DC or 220 V AC. The process connection is G1/2A as standard, with flanged versions, and a PTFE-coated fork is offered for aggressive media.
How a vibrating fork switch works
The fork vibrates at its resonant frequency in air. When the medium covers it, the added mass changes that frequency, and the electronics detect the shift and change the state of the output.
That mechanism explains most of the practical behaviour. There is no float to stick and no gap for solids to bridge, so a slurry that would jam a float switch passes the fork without effect. The switch does not need calibration to a level, because it is not measuring level; it is detecting whether the fork is covered. And it needs a minimum density to work, because a medium too light to shift the frequency will not be detected — which is the one figure the material does not give.
How to select the right switch
Medium and density. The first question is what the fork will sit in and whether it is heavy enough to shift the frequency. Water, slurries and most process liquids are well inside the range; light powders, foams and aerated media are the cases to check.
Pressure and temperature at the nozzle. The 2 MPa rating and the -30 to 150 °C fork range cover most tanks and lines. Above 150 °C the material offers a higher-temperature construction to order, and the housing stays within its own ambient limit because of the heat-break section between the fork and the electronics.
Output. A relay drives a contactor or an alarm directly. A PNP/NPN pair suits a PLC input. CAN suits a plant that already carries a bus. The choice is decided by what the signal is connected to, not by the switch.
Connection and insertion length. G1/2A is the standard thread; a flange is used where the nozzle is larger or the vessel is classified. The insertion length follows the nozzle depth, and the nozzle drawing is more use than the pipe size.
Installation and configuration
The switch is screwed or bolted into the nozzle, with the fork at the level to be detected. The material requires the cable entry to face downwards and the gland to be tightened, which is the ordinary precaution against water running down the cable into the housing.
The fork should sit clear of the nozzle wall and clear of the inlet stream, so that a falling stream or a build-up on the wall does not cover it. The material gives no minimum clearance and no insertion depth, and neither is invented here.
Measurement limitations and selection considerations
The first limitation is density. A medium too light to shift the fork frequency will not be detected, and the material does not state the threshold, so a sample should be checked before the order.
The second is build-up. A coating that bridges the two tines damps the vibration and can hold the switch in one state; the PTFE-coated form is the answer for media that tend to adhere, but it is a mitigation rather than a cure.
The third is that the switch gives no warning of drift. It is a contact, not a measurement, so a failed switch is usually found when the pump runs dry or the tank overflows. Testing the output at commissioning, and recording the state with the fork covered and uncovered, is worth more than any figure on the datasheet.
Every value below is taken from source documentation. Where a parameter is not stated in the available material it is marked as information required rather than estimated.