Product type

Pressure Switches

A pressure switch changes the state of a contact when the pressure reaches a figure that has been set. It does not report the pressure and it does not indicate it; it acts on it. The contact then drives a motor, a solenoid, an alarm or a lamp, and the fact that nothing else is required - no supply for the measurement, no controller, no loop - is the reason it remains in service on plant that has been updated around it.

What a pressure switch is

A pressure switch changes the state of a contact when the pressure reaches a figure that has been set. It does not report the pressure and it does not indicate it; it acts on it. The contact then drives a motor, a solenoid, an alarm or a lamp, and the fact that nothing else is required - no supply for the measurement, no controller, no loop - is the reason it remains in service on plant that has been updated around it.

It is worth separating the switch from what is near it, because the names are used loosely. A transmitter produces a continuous signal proportional to pressure and leaves the decision to the control system. A controller receives a signal, displays it and produces an output according to a set point held in its own electronics. A switch contains the decision itself, mechanically, and the set point is changed by turning a screw rather than by entering a number.

What decides a switch is a pair of figures rather than one. The actuation point is where the contact transfers; the differential is how far the pressure must return before it transfers back. Both are adjustable on most industrial switches, both have limits, and the pair together is what makes the device stable or useless on a given duty.

How a pressure switch measures

Pressure acts on a sensing element - a diaphragm, a bellows or a piston - and the element works against a spring. The spring force sets the pressure at which the element has travelled far enough to transfer the contacts, and the screw that adjusts it is the set point control. A second adjustment sets how far the element must travel back before the contacts return, and that is the differential, sometimes called the deadband or the reset point.

The differential is what makes a switch usable. Without a gap between the point where the contact makes and the point where it breaks, a pressure wandering either side of the set figure would cause the contact to chatter, which wears the contacts and produces nonsense at whatever it is switching. The differential is also a trade: a large one holds a state firmly but lets the pressure move further before anything happens, and a small one responds closely but is more exposed to the noise in the process.

Sensing elements differ in what they tolerate rather than in principle. A diaphragm suits low pressures and can be made from a material chosen for the medium; a piston tolerates higher pressures and is less affected by a dirty fluid; a bellows gives more travel and is common where a clear difference between the two set points is wanted. The element also decides the proof pressure the switch survives without being damaged, which is a different figure from the pressure it is set to act at.

Configuration choices

Most of the specification is fixed by these decisions rather than by the accuracy class. Each one constrains the next, which is why they are settled in order.

ConfigurationOptions to fixWhat it actually decides
Ranges, and the direction the switch can act in A range that starts below atmospheric, or one that begins above itWhether a vacuum duty is covered at all. A switch whose low end is above zero cannot be set to act on a vacuum however the screw is turned, so the direction of the process is settled before the maximum figure is discussed.
Adjustable differential The band within which the differential can be setWhether the process can run without the switch cycling. The band is normally a fraction of the range, so a range chosen far above the working pressure cannot be set finely, and one chosen too close leaves no room for the swing the process actually has.
Contact form Single pole double throw, or a simpler make-or-break arrangementHow many circuits one switch can drive and in which direction. A changeover contact lets a single device stop one circuit and start another as it transfers, which is often what removes a relay from the panel.
Reset behaviour Automatic, or manual after the contact has operatedHow the plant recovers from the condition the switch has detected. Automatic reset restores the circuit as soon as the pressure returns; a manual reset holds the state until an operator has seen and acknowledged it.
Rating, enclosure and connection Contact rating including inrush, ingress protection, and the process connectionWhether the switch survives the load and the location. A rating quoted for a resistive load does not cover a motor or a solenoid, and an enclosure rated for solid objects rather than water decides where the switch may be mounted.

How to choose a pressure switch

FactorWhy it decides the answerHow to settle it before enquiring
The pressure in both directions A switch that has to act on a vacuum is a different instrument from one that acts on positive pressure, and the two are often confused because the top of the range looks similar.State the full cycle of the process, including start-up, shutdown and any evacuation step, not only the working pressure.
The figure at which the switch should act It is the value the plant is protected by or controlled against, and it has to be settable within the band the instrument offers.Give the actuation point and say whether it should be set before dispatch or adjusted on site.
How much the pressure is allowed to move after the switch acts This is the differential, and it is what stops the switch cycling. Too small and the contact chatters; too large and the plant swings further than intended.Give the acceptable swing, or say that the factory setting is acceptable and what the process does around it.
The load being switched A contact rating is not a property of the pressure duty, and an inductive load draws far more at the moment of switching than it does once running.Give the voltage, the current and whether the load is resistive or inductive, and say how often the switch operates.
Where the switch is mounted The enclosure rating, the ambient temperature and the fluid temperature have separate limits, and the medium compatibility depends on the wetted parts.State the location, whether it is exposed to water or weather, and what the medium is, rather than assuming a general-purpose enclosure covers it.

The nearest alternatives

These are the types an enquiry for a pressure switch usually turns out to be, and the point at which the choice is genuinely decided.

Nearest alternativeWhat separates it from a pressure switch
Pressure transmitters Reports the pressure rather than acting on it, leaving the decision to the control system, where the set point can be changed without touching the instrument. Chosen where the value itself is wanted, or where the switching logic is likely to change.
Pressure controllers Reads a pressure and displays it, then produces an output against a set point held in its electronics. It can do more than one thing with the same reading, and it can be reconfigured; a switch does one thing mechanically and cannot be reprogrammed.
Vacuum pressure switches Intended for duties entirely below atmospheric, where the whole scale is usable rather than half of it being a range the process never enters.
Differential pressure switches Acts on the difference between two ports, for filter blockage and flow proving. A single-port switch cannot see a difference, so it cannot protect an element whose condition shows up as a rise in pressure drop.
Pressure gauges Indicates the pressure and does nothing with it. Where a visible reading and a switching action are both needed, the two sit side by side rather than one standing in for the other.

A switch set at a figure and a gauge at the same tapping point is a common pairing, because one acts on the pressure and the other lets an operator see why it acted.

What to include in the enquiry

The first reply can be a quotation rather than a set of questions if the enquiry carries these. Where a figure is not known, send the duty description and we will confirm what it implies.

  1. Medium and its temperature
  2. The full range the pressure passes through, in both directions
  3. The figure at which the switch should act
  4. The differential, or acceptable swing, around that figure
  5. Whether reset should be automatic or require an operator
  6. Contact function required, and the circuits it will drive
  7. Load voltage and current, and whether the load is inductive
  8. Process connection type and size, or tube size for a push-in fitting
  9. Enclosure requirement from the location
  10. Quantity, destination port and required delivery date

Available products

1 model in Pressure Switches

Rectangular pressure switch with a transparent scale window showing RANGE and DIFF marks, two adjustment screws, a metal threaded pressure port and a circular push-in fitting on the side

PK503 (3 models) · Pressure Switches

Mechanical Pressure Switch

Mechanical pressure switches with a separate set point and differential screw, SPDT contacts and automatic reset, covering vacuum down to -0.05 MPa and positive pressure to 1.0 MPa in three range versions.

Ranges
PK503 -0.05 to 0.3 MPa; PK506 -0.05 to 0.6 MPa; PK510 0.1 to 1.0 MPa
Adjustable differential
0.035 to 0.15 MPa; 0.06 to 0.4 MPa; 0.1 to 0.3 MPa respectively
Contact form
SPDT, single pole double throw, terminals 1-3-5
Reset
Automatic

Also in Pressure Measurement

Other product types in this category

Every type we quote for under Pressure Measurement. A type with no link yet is still quoted for - it is described on the Pressure Measurement overview, and gets a page of its own as soon as a model is published against it.

Frequently asked

Pressure Switches questions

What is the difference between the set point and the differential?

The set point is the pressure at which the contact transfers. The differential is how far the pressure has to come back before it transfers again. Both are usually adjustable and they interact: changing the differential moves the point at which the switch resets, and therefore where the next cycle begins. On a process that cycles continuously, the differential is the more important of the two, because it is what prevents the switch from acting many times a minute.

Why is the proof pressure not a working pressure?

Because it is the pressure the sensing element survives without being permanently damaged, not the pressure it is intended to be operated at. A switch can be briefly over-pressured to a figure well above its range and still work afterwards, but holding it there is a different matter, and setting a switch to act near the top of its own range while the plant regularly exceeds that figure is a specification error rather than a margin.

Can one switch replace a transmitter and a controller?

It can replace them where the requirement is a single fixed decision, and that is exactly the case a switch is the simpler and more robust choice for. It cannot replace them where the set point is likely to change, where several outputs have to follow the same reading, where the pressure has to be recorded, or where the reason for a trip has to be diagnosed later from data. Those needs are what a transmitter and a controller exist for.

How is the contact rating read?

Against the load actually being switched, not against the pressure duty. A rating quoted for an alternating supply and a resistive load does not transfer to a direct supply or to a motor, and the inrush a solenoid or a motor draws at the moment of switching can be many times the running current. Say what the contact will switch and how often, because contact life depends on both, and neither is fixed by the pressure side of the instrument.

What enclosure do I need?

One that suits where the switch is mounted rather than what it is measuring. An enclosure rated for solid objects only will keep debris out and will not keep water out, so a washdown area, an outdoor position or a condensing plant room needs a higher rating. The medium temperature and the ambient temperature are separate limits as well, and a switch that is comfortable on the medium can still be mounted somewhere the ambient exceeds what the instrument allows.

Quoting for Pressure Switches

Send the specification and we will confirm the matching model, availability and lead time. Minimum order quantity is 1 pc.

Request for quotation

Request a quotation - Pressure Switches

Send the technical detail and we will confirm availability, lead time and terms. In-stock items ship within 48 hours; customized specifications typically take 2-10 days. Minimum order quantity is 1 pc.

The more of this you can give us, the fewer exchanges are needed before we can quote.
No file chosen
Datasheet, drawing, BOM or photograph. One file, up to 10 MB (PDF, Office, image or ZIP).

By submitting this form you agree that we may contact you about this enquiry. We do not sell or share enquiry data. See our privacy policy.

Items held in stock are dispatched within 48 hours of order confirmation. Customized specifications are produced to order and typically ship within 2 to 10 days. Transit time then depends on the shipping method and destination.

Request a Quote WhatsApp