Pressure Gauges

A pressure gauge indicates the pressure at the point where it is mounted. It has a dial, a pointer and a connection, it needs no supply, and it sends nothing to a control system. It answers the question in front of whoever is standing at the tapping point rather than the one in the control room, and for that job it remains the simplest and most robust instrument there is.

What a pressure gauge is

A pressure gauge indicates the pressure at the point where it is mounted. It has a dial, a pointer and a connection, it needs no supply, and it sends nothing to a control system. It answers the question in front of whoever is standing at the tapping point rather than the one in the control room, and for that job it remains the simplest and most robust instrument there is.

It is worth being precise about the boundaries, because a gauge is often specified where a different instrument belongs. A transmitter produces a continuous signal and is chosen when the value has to travel, be logged or be acted on. A pressure switch produces a contact at a set point and nothing else. A gauge produces a local indication - and where that indication is the whole requirement, everything an electronic instrument adds is cost, supply and another way to fail.

What decides a gauge is not its measuring principle, which is settled, but three figures that move together: the dial size, the accuracy class available at that size, and the range list. Choosing any one of them without the others is how a gauge ends up reading a small fraction of its own scale, which is the most common reason a reading is worth less than the buyer expected.

How a pressure gauge measures

Most industrial gauges work on the bourdon principle. A curved tube with an oval cross section straightens slightly as pressure is admitted, and a linkage and a sector gear turn that small movement into the rotation of the pointer across the dial. The element is a solid metal part, with the case itself as the only barrier between the pressure and the atmosphere, which is why a gauge tolerates heat, vibration and overpressure that would damage an electronic instrument, and equally why it cannot be corrected, compensated or adjusted in service.

The accuracy class describes the whole assembly as a proportion of full scale, not the tube alone. The gear train, the bearings, the mounting of the pointer and the printing of the dial all contribute, and the same principle can be built to a finer class on a larger dial because a given angular error covers more length of scale. That is why dial size and class are quoted together on a specification rather than offered as independent choices.

Two properties follow from being mechanical, and both are worth stating plainly. The first is that the reading exists only at the dial: nothing leaves the instrument, so a gauge cannot feed a recorder, a controller or a historian. The second is that a gauge has no reference of its own. It reads against the atmosphere at the dial unless it is built as a sealed or an absolute instrument, so its zero moves with the weather and with altitude, by an amount that is irrelevant for most duties and decisive for some.

Configuration choices

Most of the specification is fixed by these decisions rather than by the accuracy class. Each one constrains the next, which is why they are settled in order.

ConfigurationOptions to fixWhat it actually decides
Dial size and accuracy class A small dial, a standard process dial, or a large dialThe two are not independent: a finer class is normally available only at the larger sizes, so choosing a size chooses the accuracy band. It also decides how far away the reading can be taken and how much room the tapping point needs.
Range and pressure reference A positive-pressure span, a vacuum span, or a compound span crossing zeroWhat the dial can show at all. A positive-pressure gauge reads a line below atmosphere as an off-scale condition, and a vacuum gauge has no scale above zero, so the reference is fixed by the duty before the maximum figure is discussed.
Range placement against the working pressure Where the normal working pressure sits on the dialWhat the class is worth in practice. The class applies to full scale, so a gauge reading near the bottom of a wide span reports a larger absolute error at the point that matters than the same gauge reading near the top of a narrower one.
Process connection Thread family, size and standard, and the material of the connectionWhether the gauge fits the port and whether it seals. Parallel and tapered threads carry the same nominal sizes and do not interchange, and the connection is usually the only wetted part the buyer thinks to specify.
Case, window and filling Case material and finish, window material, and whether the case is liquid filledWhether the gauge survives its surroundings rather than its medium. A filled case damps needle movement in a vibrating installation, and a case material chosen for a wet or corrosive environment has nothing to do with chemical compatibility of the wetted parts.

How to choose a pressure gauge

FactorWhy it decides the answerHow to settle it before enquiring
Normal working pressure It sets both the range and the portion of the dial that is actually going to be read, and therefore what the class delivers at the point of interest.State the pressure the line usually holds, not only its maximum, and the spike or test pressure it may see.
Whether the reading crosses zero A positive-pressure gauge and a vacuum gauge are different instruments, and only a compound gauge covers both in one dial.Say whether the process ever sits below atmospheric in normal operation, including start-up and shutdown.
Thread already at the tapping point It decides what will physically fit, and the connection is a part of the wetted boundary.Give the thread type and size at the port, or send a photograph of it. Note the family as well as the size, since G and R are not interchangeable.
Ambient conditions at the gauge Heat, vibration, direct sun, washdown and a corrosive atmosphere each change the case specification rather than the measurement.Describe where the gauge will be mounted, including whether it faces outdoors or is hosed down.
What happens to the reading afterwards A local indication and a signal that has to travel are different requirements, and confusing them leads to a gauge doing a transmitter job.Say whether the value has to be logged, transmitted or acted on, or only read at the point.

The nearest alternatives

These are the types an enquiry for a pressure gauge usually turns out to be, and the point at which the choice is genuinely decided.

Nearest alternativeWhat separates it from a pressure gauge
Digital pressure gauges Shows the same local reading on a display rather than on a dial, and runs from a battery. Chosen where a numeric value is wanted instead of a position of a needle, or where the reading has to be resolved more finely than a dial allows. It carries the same limitation: nothing leaves the instrument.
Pressure transmitters Produces a continuous electrical signal. Where the value has to travel to a controller, a recorder or a plant system, this is the instrument, and a gauge alongside it becomes a local check rather than the measurement.
Differential pressure gauges Reads the difference between two ports rather than one pressure against atmosphere. Used across filters, strainers and flow elements, where the useful figure is the drop rather than the line pressure - and where a single-port gauge gives no useful answer at all.
Vacuum gauges Scales from atmosphere downwards. Where the whole working range is below atmospheric, a dedicated vacuum instrument gives usable resolution where a compound dial has half its scale dedicated to a range the process never uses.
Pressure switches Produces a contact at a set point and nothing else. Correct where the requirement is to act on a pressure rather than to read it, and where a visible reading is also wanted, the two instruments sit beside each other rather than one replacing the other.

Where a gauge and a switch or a transmitter are both wanted at one tapping point, a manifold or a twin-connection block is usually tidier than two separate tappings.

What to include in the enquiry

The first reply can be a quotation rather than a set of questions if the enquiry carries these. Where a figure is not known, send the duty description and we will confirm what it implies.

  1. Normal working pressure, maximum pressure and any test or spike pressure
  2. Whether the reading crosses zero, or is entirely above or below atmospheric
  3. Dial size required, or the accuracy class the duty has to meet
  4. Thread type, size and standard at the tapping point
  5. Medium, and whether it is compatible with the wetted parts offered
  6. Ambient conditions: heat, vibration, weather and washdown
  7. Whether the process medium is one the instrument must not be used on
  8. Whether customisation of the dial face or the range is required
  9. Quantity, destination port and required delivery date

Available products

1 model in Pressure Gauges

Black cased circular pressure gauge with a white dial graduated to 1.6 MPa, a red tipped pointer and a brass threaded connection below the case

Y-60 (2 models) · Pressure Gauges

Bourdon Tube Pressure Gauge

Bourdon tube pressure gauges in 60 mm and 100 mm dial sizes with brass connections, covering vacuum to 40 MPa on the 60 mm dial and offered across a wide range list on the 100 mm dial, in iron and stainless steel cases.

Dial sizes
60 mm (Y-60) and 100 mm (Y-100); a 150 mm size is named without a parameter table
Accuracy class
2.5 class on the 60 mm dial; 1.6 class on the 100 mm dial
Range, 60 mm dial
0-0.1 MPa up to 0-40 MPa in fourteen steps, plus -0.1-0 MPa vacuum
Range, 100 mm dial
0-0.1 MPa up to 0-60 MPa listed for the series, with compound and vacuum forms

Also in Pressure Measurement

Other product types in this category

Every type we quote for under Pressure Measurement. A type with no link yet is still quoted for - it is described on the Pressure Measurement overview, and gets a page of its own as soon as a model is published against it.

Frequently asked

Pressure Gauges questions

Why is a pressure gauge not simply a cheaper transmitter?

Because the two answer different questions. A gauge tells whoever is standing next to it what the pressure is; a transmitter tells the control system. Where the reading is used by a person, a gauge is not a compromise but the correct instrument, and it needs no supply, has no electronics to fail and tolerates conditions that would end an electronic device. Where the value has to travel, no gauge will do it, and the cost difference stops being the relevant comparison.

How do I match the range to the process?

From the pressure the process normally holds rather than from its maximum. The accuracy class is a proportion of full scale, so a gauge reading a small part of its span reports a larger absolute error at the working point than a gauge sized so that the working pressure sits in the upper part of the dial. Where a maximum does have to be covered as well, the honest answer is usually to accept the wider span and state the upper figure, rather than to size the dial for a peak that occurs rarely.

Does the accuracy class apply across the whole scale?

It is stated against full scale, which means the permitted error is a fixed amount wherever the pointer happens to be. That is why a finer class is not automatically the right answer: on a narrow working band, a wider instrument of the same class may be worse at the working point than a narrower one, and on a dial read casually at a distance the class may not be the deciding figure at all. What the class does not cover is the installation - temperature, vibration, mounting torque and the thread into which the instrument is fitted all move the reading.

Why do thread types matter so much on a gauge?

Because the same nominal size exists in families that seal in different ways. A parallel thread such as G seals against a gasket or on tape across a flat face; a tapered thread such as R or NPT seals on the thread form itself. Sizes in the two families are close enough to be fitted into the wrong port, where they either leak, deform the port, or appear to seal and fail under pressure. Stating the thread family as well as the size, or sending a photograph of the existing port, removes the guesswork.

Are there media a general-purpose gauge must not be used on?

Yes, and the most important is oxygen. A general-purpose gauge whose movement has not been degreased carries lubricating grease, and grease meeting pressurised oxygen can ignite, which is why oxygen service requires an instrument made and marked for it rather than a different connection on the same gauge. The same caution applies to other strongly oxidising or combustible gases. A corrosive medium is a different question again, and there the wetted parts decide, since the dial itself never meets the process.

Quoting for Pressure Gauges

Send the specification and we will confirm the matching model, availability and lead time. Minimum order quantity is 1 pc.

Request for quotation

Request a quotation - Pressure Gauges

Send the technical detail and we will confirm availability, lead time and terms. In-stock items ship within 48 hours; customized specifications typically take 2-10 days. Minimum order quantity is 1 pc.

The more of this you can give us, the fewer exchanges are needed before we can quote.
No file chosen
Datasheet, drawing, BOM or photograph. One file, up to 10 MB (PDF, Office, image or ZIP).

By submitting this form you agree that we may contact you about this enquiry. We do not sell or share enquiry data. See our privacy policy.

Items held in stock are dispatched within 48 hours of order confirmation. Customized specifications are produced to order and typically ship within 2 to 10 days. Transit time then depends on the shipping method and destination.

Request a Quote WhatsApp