- Home
- Products
- Industrial Automation & Control
- Signal Isolators
- M2 DIN-Rail Signal Isolator
Industrial Automation & Control · Signal Isolators
DIN-Rail Signal Isolator
DIN-rail signal isolators and distributors giving 2000 Vrms isolation between input, output and supply, with 0.1%FS transmission accuracy and 10 ms response.
M2 ·
Key specifications
- Isolation
- 2000 Vrms for 1 min, no flashover, between input, output and supply
- Insulation resistance
- 100 MΩ minimum at 500 VDC
- Transmission accuracy
- 0.1%FS at 20°C
- Temperature drift
- 0.0075%FS/°C
- Response time
- 10 ms or less
- Supply
- 20 to 32 VDC
- Mounting
- 35 mm DIN rail
- Width
- 13 mm (13 × 108 × 115.6 mm)
- Weight
- Approximately 130 g
- Channel combinations
- One in and one out, one in and two out, two in and two out
A signal isolator sits between a field instrument and the control system and passes the signal through a magnetic barrier. Its purpose is not to change the value but to break the electrical path: a difference in earth potential between two ends of a plant, or a transient coupled onto a long cable, travels along a conductor, and a signal that is transferred without a conductor cannot carry either one through.
The modules on this page cover current and voltage loops from 4-20 mA and 0-20 mA through 0-5 V, 1-5 V and 0-10 V. They are 13 mm wide and mount on standard 35 mm DIN rail, which allows a group to be built in the depth of a cabinet rather than in the width. Isolation is 2000 Vrms between input, output and supply, transmission accuracy is 0.1%FS at 20°C, and response time is 10 ms or less.
Two versions are offered. The isolator passes a signal from a device that already has its own supply. The distributor supplies a two-wire or three-wire transmitter from the same module and isolates the signal on its return, which is the arrangement used when the transmitter is powered over the loop it measures.
How a signal isolator works
The isolation is magnetic rather than optical on these modules. The input signal is converted to a form that can cross a magnetic barrier, transferred, and reconstructed on the other side as the same proportional signal. Because the two sides share no conductor, a potential difference between them has no path to drive a current through the signal conductor — which is the mechanism by which an earth loop adds an offset to a reading that is otherwise correct.
Suppression of common-mode interference follows from the same arrangement. A voltage that appears on both conductors of the input pair, such as an induced voltage from a cable tray shared with a drive, is a differential of zero at the receiving end. A filter reduces such a signal; an isolation barrier removes the route by which it reached the measurement in the first place, which is why a filtered signal that still drifts when a nearby drive runs is a case for an isolator rather than a bigger filter.
The distributor version extends this to transmitters that take their power from the loop. It supplies 19 to 25 V to the loop at 30 mA or less and returns the signal through the same isolation barrier. Because the supply and the measurement are on the same module, the loop has one reference instead of two and the wiring between them disappears.
How to select the right module
Establish first whether the field device has its own supply. That single question separates the two versions: a two-wire transmitter needs the distributor, and a separately powered transmitter or source needs the isolator. Getting this wrong is not a matter of accuracy, because a two-wire transmitter connected to an isolator is simply unpowered.
Then fix the signal forms. The input and the output have to be chosen together, because the output can only be the proportional form of the input: a 4-20 mA input gives 4-20 mA or 1-5 V, and there is no setting that turns it into 0-10 V. Current and voltage outputs are not interchangeable in the field either; the change requires different hardware, so the form decided at the enquiry is the form that arrives.
Then check the load. A current output drives 400 Ω or less. A voltage output needs its load above a minimum, from 250 kΩ at 0-5 V and 1-5 V to 500 kΩ at 0-10 V, and a load below that takes the output outside its stated accuracy.
Finally settle the channels and the supply. One-in one-out, one-in two-out and two-in two-out forms are available, and the two-out form is what allows one field signal to reach a control system and a recorder without a second transmitter. The modules run from 20 to 32 VDC, and they are best kept off a supply shared with a drive.
Limitations and points to confirm
An isolator transfers a signal; it does not improve it. A measurement that is already inaccurate at the transmitter arrives inaccurate at the other end of the barrier, and the 0.1%FS figure describes what the module adds, not what the loop as a whole achieves. Where a loop has to be reconciled, the transmitter and the receiving card are the places to look first.
These modules are rated for a temperature range of -10 to 50°C and a humidity range of 25 to 85 %RH, without condensation. They are not sealed against washdown and the front face is not described as ingress protected, so they belong in a cabinet rather than on the machine. Vertical mounting helps the internal heat escape, and the modules need a gap when installed side by side.
Three items in the supplied material are incomplete and are published as such. The power consumption figures are assigned to the two versions in opposite ways in the two tables. Two different EMC references are cited for the same product. And one table leaves the response time cell blank. Where an application has to be documented against a particular standard or a particular consumption figure, tell us and we will confirm which reference applies rather than choosing one here.
The supplied document does not state whether an intrinsically safe version exists. A loop that enters a hazardous area is therefore a case to confirm before it is ordered rather than a case this page can answer.
Features
- 2000 Vrms isolation between input, output and supply, which is what breaks an earth loop rather than filtering it
- 0.1%FS transmission accuracy at 20°C, so a signal can be isolated without changing the value the control system sees
- A 13 mm wide housing, which allows a dense group on a standard 35 mm DIN rail
- Pluggable terminals, so a module can be changed without disturbing the wiring to the field
- A distributor version that supplies a two-wire transmitter from the same module that isolates its signal
- One-in two-out channel forms, so one field signal can feed a control system and a recorder at the same time
- A response time of 10 ms or less, fast enough for a loop that is also used for control rather than only for indication
- Pluggable range of input and output forms covering 4-20 mA, 0-20 mA, 0-5 V, 1-5 V and 0-10 V
Technical specifications
Every value below is taken from source documentation. Where a parameter is not stated in the available material it is marked as information required rather than estimated.
| Current input | 4-20 mA, 0-20 mAStandard |
|---|---|
| Voltage input | 0-5 V, 1-5 V, 0-10 V; isolator version onlyStandard |
| Input impedance, current | 50 Ω or lessStandard |
| Input impedance, voltage | 250 kΩ or moreStandard |
| Maximum input current | 30 mA or lessStandard |
| Maximum input voltage | 10.5 V or less, voltage isolator versionStandard |
| Distributor output to transmitter | 19 to 25 V at 30 mA or less; distributor version onlyStandard |
| Field device compatibility, isolator | DC voltage or current source that already has its own supplyStandard |
| Field device compatibility, distributor | Two-wire and three-wire transmitters, and DC current sourcesStandard |
| Output signal | 4-20 mA, 0-20 mA, 0-5 V, 1-5 V, 0-10 VStandard |
|---|---|
| Current output load, current isolator | RL 400 Ω or less at 4-20 mA and 0-20 mAStandard |
| Voltage output load, current isolator | RL 250 kΩ or more at 0-5 V and 1-5 V; 500 kΩ or more at 0-10 VStandard |
| Voltage output load, voltage isolator | RL 20 kΩ or more at 0-5 V, 1-5 V and 0-10 VStandard |
| Input-to-output proportionality | An input can only be converted to the proportional output form; 4-20 mA in, for example, gives 4-20 mA or 1-5 V out, not 0-10 VStandard |
| Current and voltage output switching | Not switchable in the field; requires a hardware change, so the form must be stated at orderStandard |
| Supply voltage | 20 to 32 VDCStandard |
|---|---|
| Power consumption, isolator | 0.8 W or less single channel; 1.0 W or less dual channelStandard |
| Power consumption, distributor | 1.5 W or less single channel; 2.6 W or less dual channelStandard |
| Power consumption conflict | The two parameter tables in the supplied document assign these figures to the opposite versionsInformation required |
| Insulation resistance | 100 MΩ or more at 500 VDC, between input, output and supplyStandard |
| Dielectric strength | 2000 Vrms for 1 minute with no flashover, between input, output and supplyStandard |
| Surge protection | 1 kV differential mode, 2 kV common modeStandard |
| EMC immunity | Fast transient burst ±2 kV on supply and ±1 kV on signal; electrostatic discharge 4 kV contact and ±8 kV air; surge ±1 kVStandard |
| EMC standard cited (first table) | GB/T 18268, cited as equivalent to IEC 61326-1Standard |
| EMC standard cited (second table) | IEC 61000-6-1 and IEC 61000-6-3Information required |
| Operating temperature | -10 to 50°C, without condensation or ice formationStandard |
|---|---|
| Operating humidity | 25 to 85 %RHStandard |
| Storage temperature | -10 to 60°C, without condensation or ice formationStandard |
| Mounting | 35 mm DIN railStandard |
| Dimensions | 13 × 108 × 115.6 mm (width × height × depth)Standard |
| Weight | Approximately 130 gStandard |
| Terminals | PluggableStandard |
| Front panel | Supply indicator lampStandard |
| Intrinsic safety for hazardous areas | Information required; the document does not state whether an intrinsically safe version existsInformation required |
| Scope | Additional forms supplied in November 2026 for this product type. Figures below are from that batch; where they differ from the rows above, both are recorded rather than merged.Standard |
|---|---|
| Channel configurations | One-in/one-out and one-in/two-outStandard |
| Input | 4-20 mA, 0-10 V, 0-5 V, RTD and thermocoupleStandard |
| Output | 4-20 mA, 0-10 V, relay contacts and RS-485/ModbusStandard |
| Supply | 24 V DCStandard |
| Ambient temperature | -20 to 60 CStandard |
| Explosion-proof barrier form | Intrinsically safe barrier versions are included in the batch for hazardous-area circuitsStandard |
Available models
| Model | Configuration | Key ranges | Availability |
|---|---|---|---|
| M21 | Isolator | 4-20 mA, 0-20 mA, 0-5 V, 1-5 V, 0-10 V in and out | For voltage and current sources that already have their own supply |
| M23 | Distributor | 4-20 mA and 0-20 mA in; 19 to 25 V at 30 mA or less out to the transmitter | Supplies two-wire and three-wire transmitters from the same module |
| One in, two out | Channel form | Signal distribution | One field signal feeding two destinations |
| Two in, two out | Channel form | Two independent channels | Highest channel density of the forms offered |
Certification and compliance
Certification documents not yet supplied
Certifications are only published once a certificate copy can be produced, so this section is deliberately empty rather than populated with assumed approvals. Tell us which approvals your application requires and we will confirm what is available for this instrument.
Parameters still to be confirmed
The following are required for a complete specification but are not stated in the documentation supplied to us. They are listed rather than estimated:
- Whether an intrinsically safe version exists for hazardous areas
- Attribution of the two power-consumption figures, which the supplied tables assign to opposite versions
- Which EMC standard applies, since two different references are given
- Response time of the certified isolator variant, where the supplied table is blank
- Meaning of the certification named in the supplied document, and the certificate number and issuing body
- Voltage output load figure that applies to the isolator version (the two tables differ)
- Certification list and availability of certificate copies
- Warranty period and the terms that apply
- English-language datasheet and manual in PDF form
- Packaging dimensions and gross weight for freight calculation
- Terminal torque and recommended wire gauge
Frequently asked questions
Isolator or distributor — which one does the application need?
It depends on whether the transmitter has its own supply. A two-wire transmitter takes its power over the same pair that carries its signal, so it needs a distributor: the M23 supplies 19 to 25 V to the loop and isolates the signal on the way back. A transmitter or a source that already has a separate supply feeds an isolator, which is the M21. The two are not interchangeable. Connecting a two-wire transmitter to an isolator leaves it unpowered, and connecting a separately powered source to a distributor means two supplies are fighting over the loop.
Can the input and output forms be changed later?
No. Changing between a current and a voltage output is a hardware change, not a setting, so the form has to be stated when the order is placed. There is a second constraint on the same point: an input can only be converted to the proportional output form. A 4-20 mA input gives a 4-20 mA or a 1-5 V output, and it cannot be set to give 0-10 V. Both the input and the output therefore have to be decided together rather than one at a time.
What does the output load figure mean in practice?
It is the resistance the output can drive while still holding the stated 0.1%FS accuracy. A current output drives 400 Ω or less, which is enough for a receiving instrument and the cable to it. A voltage output needs its load to be above a minimum rather than below a maximum, because the output is a source: at 0-5 V and 1-5 V the load has to be 250 kΩ or more, and at 0-10 V it has to be 500 kΩ or more. A load outside those ranges takes the output away from the stated accuracy rather than damaging it.
What is needed to quote the right module?
State the signal coming from the field and whether that device has its own supply, the signal the receiving equipment expects, how many channels are needed and in which combination, and the supply voltage available in the cabinet. If the receiving equipment is a control system with a particular input card, say which, because the input and output forms have to be decided together and cannot be changed afterwards.
Is an intrinsically safe version available?
The supplied document does not state whether one exists, so this page does not claim it does. If the isolator has to sit on a loop that enters a hazardous area, say so when enquiring and we will confirm what is available and what documentation would come with it, rather than assuming the standard version covers that case.
Request a quotation for the M2
Send the configuration you need and we will confirm availability, lead time and terms. Minimum order quantity is 1 pc.
Request for quotation
Request a quotation - M2
Send the technical detail and we will confirm availability, lead time and terms. In-stock items ship within 48 hours; customized specifications typically take 2-10 days. Minimum order quantity is 1 pc.